Procedure 30 – Electrical Safe Work Practices

REV. 8

Revision History

Revision

Date

Comments

1

10-16-00

Initial Issue

2

03-26-03

Added electronic links

3

01-01-12

Revisions per NFPA 70E – 2009 edition (complete re-write)

4

03-16-12

Renumber and reformat procedure

5

05-16-12

Revised per NPFA 70E – 2012 edition

6

09-15-15

Revisions per NFPA 70E – 2015 edition

7

05-20-20

Revision per NFPA 70E – 2018 edition

8

09-29-20

Added Bucket and Digger Truck Safety Checklists

1.0 PURPOSE
To eliminate and control hazards in the workplace that are associated with work performed on, or near, energized and de-energized electrical equipment and circuits that operate at 50 volts and greater and to protect workers from accidental exposure to electrical shock and arc flash.

2.0 SCOPE
This procedure applies to all Nitro Construction Services employees, contractors, and visitors. It is the policy of Nitro Construction Services to provide safe working conditions for all work performed on or near electrical equipment and circuits that operate at 50 volts and greater. This is accomplished through education, training, and proper protective equipment and tools.

3.0 REFERENCES
NFPA 70E, Standard for Electrical Safety Requirements for Employee Workplaces – Part II, Safety-Related Work Practices.
NFPA 70E, Standard for Electrical Safety in the Workplace® – Part I. 2018 Edition.
NFPA 70E Handbook for Electrical Safety in the Workplace ®. 2018 Edition.
OSHA 29 CFR §1910 Subpart S, Electrical Safety-Related Work Practices.
OSHA 29 CFR §1910.269, Electric Power Generation, Transmission, and Distribution.
OSHA 29 CFR §1910.137, Electrical Protective Equipment.
OSHA 29 CFR §1926 Subpart K, Electrical Safety-Related Work Practices.

Note: If situations arise that are not covered by this policy, then-current standards and industry practices will be consulted for guidance in that situation.

4.0 DEFINITIONS
4.1 Arc Rating – The value attributed to materials that describe their performance to exposure to an electrical arc discharge. The arc rating is expressed in cal/cm2 and is derived from the determined value of the arc thermal performance value (ATPV) or energy of breakdown threshold (EBT) (should a material system exhibit a breakdown response below the ATPV value). Arc rating is reported as either ATPV or EBT, which is the lower value.
4.2 Boundary, Limited Approach – An approach limit at a distance from an exposed energized electrical conductor or circuit part within which a shock hazard exists.
4.2.1 The limited approach boundary is a shock protection boundary that is not related to arc flash or incident energy.
4.2.2 This boundary defines the approach limit for unqualified employees and is intended to eliminate the risk of contact with an exposed energized electrical conductor or circuit part.
4.3 Boundary, Restricted Approach – An approach limit at a distance from an exposed electrical conductor or circuit part within which there is an increased likelihood of electric shock, due to electrical arc over combined with inadvertent movement, for personnel working in close proximity to the energized electrical conductor or circuit part.
4.3.1 This shock protection boundary is the approach limit for qualified employees.
4.3.2 A qualified employee required to cross the restricted approach boundary must be protected from unexpected contact with the conductor or circuit part.
4.4 De-energized – Free from any electric connection to a source of potential difference and from electric charge.
4.5 Energized – Electrically connected to, or is, a source of voltage.
4.6 Exposed Worker – Person performing an electrical task.
4.7 Equi-potential Zone – Temporary protective grounding devices that have been placed at specific locations and arranged in a manner to provide a work zone that prevents each employee from being exposed to hazardous differences in electrical potential (voltage) in the event that de-energized circuits or equipment are inadvertently energized.
4.8 Exposed Energized Parts – Electrical equipment and circuits which are not guarded or isolated, that are electrically connected to a source of potential difference (voltage), or electrically charged so as to have a potential significantly different from earth.
4.9 FRC – Fire Retardant Clothing approved by Nitro Construction Services, LLC.
4.10 Full Electrical PPE – Full Electrical PPE includes: FRC, safety glasses, flash suit with hood and face protection, hearing protection, and insulated gloves with leather protectors that are properly rated for voltage present.
Note: For switching activities where no shock hazard exists, Nomex/flame retardant gloves may be used in place of insulated gloves.
4.11 Guarded – Covered, shielded, fenced, enclosed, or protected by suitable covers, casings, barriers, rails, screens, mats, or platforms to remove the likelihood of approach or contact by persons or objects to a point of danger.
4.12 Manhole – A subsurface enclosure that personnel may enter and which is used for the purpose of installing, operating, and maintaining electrical cable.
4.13 Minimum Approach Distance – The closest distance a person is permitted to approach exposed energized parts.
4.14 Overload – Operation of equipment in excess of the normal full-load rating, or of a conductor in excess of rated ampacity, which when it persists for a sufficient length of time, would cause damage or dangerous overheating. A fault, such as a short circuit or ground fault, is NOT an overload.
4.15 Portable Electric Equipment – Cord and plug-connected equipment including flexible cord sets (extension cords).
4.16 Qualified Person – A person who is trained and knowledgeable in the construction and operation of electrical equipment and who has been trained to recognize the hazards associated with electrical equipment. It is very possible for an individual to be considered “qualified” for certain electrical equipment in the workplace, but “unqualified” for other equipment.
4.17 Risk Assessment – An overall process that identifies hazards, estimates the potential severity of injury or damage to health, estimates the likelihood of occurrence of injury or damage to health and determines if protective measures are required.
4.18 Safety Glasses – ANSI-approved (Z-87) safety glasses with side shields.
4.19 Unqualified Person – A person who has little or no training to work on, or near electrical equipment and has limited or no knowledge of the hazards associated with electrical equipment.
4.20 Working On (energized electrical conductors or circuit parts) – Coming in contact with energized electrical conductors or circuit parts with the hands, feet, or other body parts, with tools, probes, or with test equipment, regardless of personal protective equipment a person is wearing. There are two categories of “working on”: Diagnostic (testing) is taking readings or measurements of electrical equipment with approved test equipment that does not require making any physical change to the equipment; repair is any physical alteration of electrical equipment (such as making or tightening connections, removing or replacing components, etc.).

5.0 RESPONSIBILITIES
5.1 Management and Supervision shall be responsible for the following:
5.1.1 Ensure that people have the necessary skills, training, PPE, tools, and equipment to safely and effectively follow the requirements of this procedure as it pertains to their job description and responsibilities.
5.1.2 Availability of the correct tools for operation and maintenance
5.1.3 Provision of complete and accurate circuit diagrams and other published information to the employee prior to the employee starting work.
5.1.4 Provision for adequate and proper illumination of the work area.

5.2 Employees are responsible for the following:
5.2.1 Following and understanding the requirements of this procedure as it applies to their job description and responsibilities.
5.2.2 Understanding the hazards associated with the work.
5.2.3 Being continuously alert and aware of the possible hazards.
5.2.4 Using the proper tools and procedures for the work.
5.2.5 Informing the employer of malfunctioning protective measures.
5.2.6 Examining all documents provided by the employer relevant to the work.
5.2.7 Maintaining good housekeeping around the equipment and workspace.
5.2.8 Reporting any hazardous incident.
5.2.9 Using and appropriately maintaining the PPE and tools required to perform the work safely.

6.0 PROCEDURE
6.1 General Work Practices
6.1.1 All energized parts to which persons may be exposed must be de-energized before any person works on or near unless it can be demonstrated that de-energizing introduces “increased or additional hazards” or is “not feasible” due to equipment design or operational limits.
6.1.1.1 Examples of “increased or additional hazard” may include, but not necessarily be limited to the following:
6.1.1.1.1 Deactivation of emergency alarm systems.
6.1.1.1.2 Shutdown of hazardous location ventilation equipment.
6.1.1.1.3 Removal of illumination for an area.
6.1.1.2 Examples of “not feasible” may include, but not necessarily be limited to the following:
6.1.1.2.1 Testing of electric circuits that can only be performed with the circuit energized.
6.1.1.2.2 Work on circuits that are essential to a continuous industrial process.
6.1.1.3 Energized parts that operate at less than 50 volts to ground need not be de-energized if there will be no increased exposure to electrical burns or explosion due to electrical arcs.
6.1.2 Conductors and parts of electric equipment that have been de-energized but have not been locked out or tagged in accordance with the Nitro Construction Services Lockout/Tagout Policy or the adopted policy of a particular project, or client, and the specific requirements in this procedure, will be treated as energized.

6.2 Working On or Near Exposed De-energized Parts (De-energizing/Re-energizing)
6.2.1 De-energizing Equipment
6.2.1.1 Procedures for safely de-energizing circuits and equipment must be determined before equipment can be de-energized.
6.2.1.2 All energy sources for the equipment to be worked on must be disconnected. Push buttons, selector switches, interlocks, and other control circuit devices may not be used as the sole means for disconnection circuits or equipment.
6.2.1.3 Interlocks for electrical equipment may not be used as a substitute for a lockout device or tag.
6.2.1.4 All capacitors, other high capacitance elements, and any line to which capacitors are connected will be discharged, short-circuited, and grounded if the stored electrical energy might endanger personnel. Such items will be treated as energized while performing this task.
6.2.1.5 All stored mechanical energy in devices that could re-energize electric circuit parts will be blocked or relieved to prevent accidentally energizing by the device.
6.2.1.6 A lock and tag will be placed on each energy source used to de-energize circuits and equipment on which work is to be performed. De-energization must be performed in accordance with the Nitro Construction Services Lockout/Tagout Procedure or the adopted policy of a particular project or client. A lock or tag may only be used independently under the following conditions:
6.2.1.6.1 If a lock cannot be applied, a tag used without a lock is only permitted when supplemented by at least one additional safety measure that provides a level of safety equivalent to that obtained using a lock. Examples of additional safety measures may include, but not necessarily be limited to the following:
6.2.1.6.1.1 Removal of an isolation circuit element.
6.2.1.6.1.2 Blocking of a controlling switch.
6.2.1.6.1.3 Opening of an extra disconnection device.
6.2.1.6.2 A lock may never be used without a tag.
6.2.1.7 All complex lockout/tag out procedures shall require a written plan of execution that identifies the person in charge. Each complex lockout/tag must be under the direct control of a single person who is identified in the written plan.
6.2.1.7.1 A complex lockout/tag out plan shall be permitted where one or more of the following exist:
6.2.1.7.1.1 Multiple energy sources
6.2.1.7.1.2 Multiple crews
6.2.1.7.1.3 Multiple crafts
6.2.1.7.1.4 Multiple locations
6.2.1.7.1.5 Multiple employers
6.2.1.7.1.6 Different disconnecting means
6.2.1.7.1.7 Particular sequence
6.2.1.7.1.8 A job or task that continues for more than one work period
6.2.1.8 A qualified person must operate the equipment controls to verify that the equipment cannot be restarted.
6.2.1.9 Utilizing the proper personal protective equipment, a qualified person must use approved test equipment to test the circuit elements and electrical parts of equipment to which employees will be expose; to verify that the circuit elements and equipment parts are de-energized. The test will determine if any energized condition exists because of induced voltage or voltage back feed. The following steps must be used to ensure that electrical equipment has been safely and effectively de-energized:
6.2.1.9.1 The approved test equipment must be visually inspected for proper operation and insulation integrity.
6.2.1.9.2 The qualified person must check the approved test equipment on a known energized source or an approved “test set” in order to verify the proper operation of the test equipment.
6.2.1.9.3 Using the approved test equipment, check that the electrical equipment or circuits in question have been de-energized.
6.2.1.9.4 The approved test equipment must be re-check on a known energized source or an approved “test set” immediately after the test to reconfirm the proper operation of the test equipment.

6.2.1.10 The following shall be required for grounding equipment:
6.2.1.10.1 Temporary protective grounds shall be placed at such locations and arranged in such a manner as to prevent each employee from being exposed to hazardous differences in electrical potential.
6.2.1.10.2 Temporary protective grounds shall be capable of conducting the maximum fault current that could flow at the point of grounding for the time necessary to clear the fault.
6.2.1.10.3 Temporary protective grounds shall have an impedance low enough to cause immediate operation of protective devices in case of accidental energizing of the electric conductors or circuit parts.
6.2.1.10.4 Until the line or equipment has been effectively grounded, all exposed circuits and parts will be treated as energized. Thus, the appropriate work practices, PPE, and tools must be utilized prior to and during the installation of the protective grounding equipment.
6.2.1.10.5 Prior to installing grounds, equipment must be tested to ensure the voltage is absent unless a previously installed ground is already in place.
6.2.1.10.6 Whenever possible, live-line tools or hot sticks must be used to attaché or remove ground connections from lines and equipment unless the design of the equipment does not permit the use of such tools or equipment.
6.2.1.10.7 Order of connection – When attaching a ground to a line or piece of equipment, the ground-end connection must be attached first.
6.2.1.10.8 Order of removal – When removing grounds, first remove the protective grounding equipment from the line or equipment before removing the ground-end connection.
6.2.1.10.9 Grounds may be temporarily removed for testing; however, the equipment must be treated as energized while grounds are not attached.
6.2.1.10.10 If grounding is demonstrated to be impractical or the conditions resulting from the installation of grounding equipment would present greater hazards than working without grounds, the equipment may be treated as de-energized if all of the following conditions are met:
6.2.1.10.10.1 The equipment has been locked out in accordance with the Nitro Construction Services Lockout/Tagout Procedure or the adopted policy of a project or client.
6.2.1.10.10.2 There is no possibility of contact with another energized source.
6.2.1.10.10.3 The hazard of induced voltage is not present.
6.2.2 Re-energizing Equipment
Before re-energizing electrical equipment on which electrical work has been performed, the following requirements must be met in the order given:
6.2.2.1 Testing and a visual inspection must be conducted by a qualified person to verify that all tools, electrical jumpers, shorts, grounds, and other such devices have been removed.
6.2.2.2 All employees exposed to the hazards associated with re-energizing the equipment must be warned to stay clear of the circuits and equipment.
6.2.2.3 Each lock and tag must be removed by the person who applied it or by another qualified person in accordance with the Nitro Construction Services Lockout/Tagout Procedure or the adopted policy of a particular project or client.

6.3 Working On or Near Exposed Energized Parts (Requirements)
6.3.1 General Requirements
6.3.1.1 All energized parts to which persons may be exposed must be de-energized before any person works on or near unless it can be demonstrated that de-energizing introduces increased or additional hazards or is not feasible due to equipment design or operational limits.
6.3.1.2 Only qualified persons may work on electrical conductors or circuit parts that have not been put into electrically safe work conditions.
6.3.1.2.1 Appropriate safety-related work practices shall be determined before any person is exposed to the electrical hazards involved by using both shock risk assessment and arc flash assessment.
6.3.1.3 Where work is performed in locations containing uninsulated energized overhead lines that are not guarded or isolated, precautions shall be taken to prevent employees from contacting such lines directly with any unguarded parts of their body or indirectly through conductive materials, tools, or equipment.
6.3.1.4 A qualified person shall determine if the overhead electrical lines are insulated for the lines’ operating voltage.
6.3.1.5 Minimum approach distances for unqualified persons – When an unqualified person must work in an elevated position in close proximity to energized overhead lines or exposed energized electrical equipment, the location must be such that the person and the longest conductive object he or she may contact cannot come closer to any unguarded, energized overhead line or exposed electrical equipment then the following minimum approach distances:
6.3.1.5.1 For voltages to ground 50kV (87kV phase-to-phase) or below must be 10 feet.
6.3.1.5.2 For voltages to ground over 50kV (87kV phase-to-phase) must be 10 feet plus 4 inches for every 10kV (17kV phase-to-phase) over 50kV.
6.3.2 Requirements for Qualified Employees
6.3.2.1 An approved Energized Work Permit (see Table E in this procedure) is required under the following conditions:
6.3.2.1.1 When work is performed within the restricted approach boundary.
6.3.2.1.2 When the employee interacts with the equipment when conductors or circuit parts are not exposed but an increased likelihood of injury from exposure to an arc flash hazard exists.
6.3.2.2 Exemptions to Energized Work Permit
6.3.2.2.1 An energized electrical work permit shall not be required if a qualified person is provided with and uses appropriate safe work practices and required PPE under any of the following conditions:
6.3.2.2.1.1 Testing, troubleshooting, and voltage measuring;
6.3.2.2.1.2 Thermography and visual inspections if the restricted approach boundary is not crossed;
6.3.2.2.1.3 Access to and egress from an area with energized electrical equipment if no electrical work is performed and the restricted approach boundary is not crossed;
6.3.2.2.1.4 General housekeeping and miscellaneous non-electrical tasks if the restricted approach boundary is not crossed.
6.3.2.3 Working Clearances
6.3.2.3.1 When a qualified person is working in close proximity to exposed energized parts or energized overhead lines, whether in an elevated position or on the ground, they may not approach or take any conductive object closer to the energized part then the minimum approach distances given in Table A.
6.3.2.3.2 A qualified person, wearing the appropriate flash protection, may work closer to exposed energized parts or overhead lines than the minimum approach distances given in Table A if at least one of the following additional protective measures has been taken:
6.3.2.3.2.1 The person is insulated from the energized part by gloves and/or insulated sleeves rated for the correct voltage.
6.3.2.3.2.2 The energized part is insulated from all other conductive objects at a different potential and from the person.
6.3.2.3.2.3 The person is insulated from all conductive objects at a potential different from that of the energized part.
6.3.2.3.3 If one or more qualified persons are performing work inside the minimum approach boundaries defined in Table A, all other persons required to work inside the corresponding flash protection boundaries (also listed in Table A), MUST wear the appropriate PPE to protect against potential electrical arc and blast hazards.
6.3.2.4 Overhead Lines – Where work is to be performed in locations containing uninsulated energized lines that are not guarded or isolated, precautions shall be taken to prevent employees from contacting such lines directly with any unguarded parts of their body or indirectly through conductive materials, tools, or equipment. Where the work to be performed is such that contact with uninsulated energized overhead lines is possible, the lines shall be de-energized and visibly grounded at the point of work, or suitably guarded.
6.3.2.5 Working space about electrical equipment – Areas around electrical equipment, with emphasis on those equipment installations that have access doors and panels, must be kept clear of materials, equipment, or any other articles that deter access to the electrical equipment.
6.3.2.6 Illumination – Employees may not enter or perform work near exposed energized parts unless there is adequate lighting to perform the job safely. In addition, employees should never reach blindly into areas that may contain energized parts.
6.3.2.7 Confined or enclosed workspaces – Protective shields, barriers, or insulating materials shall be used to avoid accidental contact with exposed energized parts when working in confined or enclosed spaces. In addition, doors and hinged panels must be secured to prevent them from swinging into the person and causing contact with exposed energized parts operating at 50 volts or more or where an electrical hazard exists if the movement of the door or hinged panel is likely to create a hazard.
6.3.2.8 Conductive materials and equipment – Conductive materials and equipment must be handled in a manner to prevent bodily contact with energized parts. If long dimensional conductive objects (such as ducts and pipes) must be handled in areas with exposed energized parts, the employee shall wear insulating gloves suitable for the voltage of the exposed part, and/or the exposed part shall be physically isolated to minimize the hazard.
6.3.2.9 Portable ladders – Only portable ladders with nonconductive side-rails are permitted to be used where the ladder or person could contact exposed energized parts.
6.3.2.10 Conductive apparel – Conductive clothing and jewelry (e.g. rings, watch bands, earrings, necklaces, key chains, etc.) must not be worn within the restricted approach boundary or if they might contact exposed energized parts.
6.3.2.11 Housekeeping duties – Employees shall not perform housekeeping duties inside the restricted approach boundary where there is a possibility of contact with energized electrical conductors or circuit parts unless adequate safeguards (such as insulating equipment or barriers) are provided to prevent contact. Electrically conductive cleaning materials (including conductive solids such as steel wool, metalized cloth) shall not be used in proximity to exposed energized parts. Flammable cleaning solvents shall not be used on energized electrical parts.
6.3.2.12 Safety Interlocks – Only a qualified person following the requirements for working inside the restricted approach boundary may defeat or bypass an electrical safety interlock over which the person has sole control, and then only temporarily while the qualified person is working on the equipment. The safety interlock system must be returned to its operable condition when the work is completed.
6.3.2.13 Working position – Each person, to the extent that other safe work practices permit, must work in a position from which a slip or reaction to a shock will not bring the person into contact with exposed energized parts.
6.3.2.14 Covered (non-insulated) conductors – The requirements of this section also apply to work being performed in the proximity of covered (non-insulated) conductors.
6.3.2.15 Draw-out type circuit breakers – When draw-out type circuit breakers are removed or inserted, the breaker must be in the “open” position and the control circuit must be rendered inoperable, if the design of the equipment permits.
6.3.2.16 Current transformer secondaries – The secondary of a current transformer may not be opened while the transformer is energized. If the primary of the current transformer cannot be de-energized before work is performed on an instrument, a relay, or other section of a current transformer secondary circuit, the circuit must be “bridged” so that the current transformer secondary will not be opened.
6.3.2.17 Generator brushes – When replacing generator brushes while the generator is energized, the circuit must first be checked to ensure a ground condition does not exist.
6.3.2.18 Personal protective grounds – A conductor, device, and/or switch that is intentionally installed (clamped, closed, inserted) between a known grounding system (bus or frame) and a de-energized, locked out and/or isolated electrical part.
6.3.2.18.1 Temporary ground – a ground that is momentarily applied (touched) to drain off static, induced, or capacitive charges.
6.3.2.18.2 Safety ground – a ground that is installed (clamped, closed grounding switch, etc.) for the duration of the work period.
6.3.2.18.3 Test ground – A ground that is installed (clamped) for a short or finite period of time to facilitate testing.
6.3.3 Requirement for Using Vehicular and Mechanical Equipment
6.3.3.1 Any vehicle or mechanical equipment capable of having parts of the structure elevated near energized overhead lines must be operated so that a clearance of at least 10 feet is maintained. If the voltage is higher than 50kV (87kV phase-to-phase), the clearance must be increased 4 inches for every 10kV (17kV phase-to-phase) over 50kV. However, under any of the following conditions, the clearance may be reduced:
6.3.3.1.1 If the vehicle is in transit with its structure lowered, the clearance may be reduced to 4 feet 9 SME (50kv rule applies).
6.3.3.1.2 If properly rated insulating barriers are installed on the energized lines, the clearance may be reduced to a distance that is within the designed working dimensions of the insulating barrier.
6.3.3.1.3 If the equipment is an aerial lift insulated for the voltage present and if the work is performed by a qualified person the clearance between the uninsulated portion of the aerial lift and the overhead line may be reduced to the minimum approach distance given in Table A.
6.3.3.2 Employees standing on the ground may not contact the vehicle or mechanical equipment or any of its attachments, unless:
6.3.3.2.1 The person is using protective equipment rated for the voltage present; OR
6.3.3.2.2 The equipment is located so that no uninsulated part of its structure can come closer to the line than permitted by this section.
6.3.3.3 If the vehicle or equipment has been intentionally grounded, employees working on the ground may not stand at the grounding location if there is a possibility of overhead line contact. Additional precautions such as the use of barricades or insulation must be taken to protect employees from hazardous ground potentials if necessary.

6.4 Arc Flash Risk Assessment
6.4.1 An arc flash risk assessment shall be performed and shall determine if an arc flash hazard exists.
6.4.1.1 If the arc flash hazard exists, the risk assessment shall determine the appropriate safety-related work practices, the arc flash boundary, and the personal protective equipment that people within the arc flash boundary shall use.
6.4.2 The arc flash risk assessment shall take into consideration the design of the overcurrent protective device and its opening time, including its condition of maintenance.
6.4.3 Completion of the arc flash risk assessment is the responsibility of the facility owner.
6.4.4 The arc flash boundary for systems 50 volts and greater shall be the distance at which the incident energy equals 5 J/cm2.
6.4.5 Arc-rated clothing and other PPE shall be used by the employee based on the incident energy exposure associated with the specific task.
6.4.6 Equipment Labeling – The owner of the electrical equipment shall be responsible for the documentation, installation, and maintenance of the field-marked label. Electrical equipment such as switchboards, panelboards, industrial control panels, meter socket enclosures, and motor control centers that are in other dwelling units, and are likely to require examination, adjustment, servicing, or maintenance while energized, shall be field marked with a label containing all of the following information:
6.4.6.1 At least one of the following:
6.4.6.1.1 Available incident energy and the corresponding working distance.
6.4.6.1.2 Minimum arc rating of clothing
6.4.6.1.3 Required level of PPE
6.4.6.1.4 Highest Arc Flash PPE category for the equipment
6.4.6.2 Nominal system voltage
6.4.6.3 Arc flash boundary

6.5 Shock Risk Assessment
6.5.1 A shock risk assessment shall determine the voltage to which personnel with being exposed, the boundary requirements, and the PPE necessary in order to minimize the possibility of electric shock to personnel.
6.5.2 Completion of the shock risk assessment is the responsibility of the facility owner.
6.5.3 The shock protection boundaries identified as limited approach boundary and restricted approach boundary shall be applicable where approaching personnel is exposed to energized electrical conductors or circuit parts.
6.5.3.1 The limited approach boundary is the approach limit for unqualified persons. Only qualified persons should be permitted to be within the space defined by the limited approach boundary.
6.5.3.2 The restricted approach boundary is the closest approach distance for a qualified person without the use of personal or shock protective equipment.

6.6 Safeguards for Personal Protection
6.6.1 Use of personal protective equipment (PPE)
6.6.1.1 All PPE utilized by employees shall be in compliance with the Standards associated with that type of equipment. (see Table C below, as a reference from NFPA 70E 130.7(C)(15)(c)
6.6.1.2 When an employee is working within the restricted approach boundary, the worker shall wear the appropriate personal protective equipment. (See Table B)
6.6.1.3 PPE shall be properly stored and maintained in a safe, reliable condition and shall be inspected prior to each use.
6.6.1.4 Garments that are not arc-rated shall not be permitted to be used to increase the arc rating of a garment or of a clothing system.
6.6.1.5 Clothing shall cover potentially exposed areas as completely as possible. Shirt and coverall sleeves shall be fastened as the wrists, shirts shall be tucked into pants, and shirts, coveralls, and jackets shall be closed at the neck.
6.6.1.6 Arc-rated apparel shall fit properly such that it does not interfere with the work task. Tight-fitting clothing shall be avoided. Loose-fitting clothing provides additional thermal insulation because of air spaces.
6.6.1.7 Arc-rated apparel shall be inspected before each use. Work clothing or arc flash suits that are contaminated or damaged to the extent their protective qualities are impaired, shall not be used. Protective items that have been contaminated with grease, oil, or flammable liquids or combustible materials shall not be used.
6.6.1.8 The garment manufacturer’s instructions for care and maintenance of arc-rated apparel shall be followed.
6.6.1.9 Electrical PPE, designed to protect employees from electrical shock and flash hazards, is required when work is performed on or near exposed energized or potentially energized electrical circuits and parts under any of the following conditions:
6.6.1.9.1 When a person must work directly on exposed energized equipment (the intent to make contact exists).
6.6.1.9.2 When a person must enter or take any conductive object inside the limited approach distances given in Table 130.4(D)(a) & (b).
6.6.1.9.3 When a person must be inside the restricted approach boundary (as listed in Table 130.4(D)(a) & (b) and work is being performed that may inadvertently cause contact with energized parts or cause an electrical fault.
6.6.1.10 Rubber-insulating gloves shall be rated for the voltage for which the gloves will be exposed.
6.6.1.11 If the insulating capability of protective equipment may be subject to damage during use, the insulating material must be protected.
6.6.1.12 Protective barriers, shields, or insulating materials must be used to protect employees from electrical shock, burns, or other related injuries while working near exposed energized parts that might be accidentally contacted or where possible dangerous electrical arcing or electric heating may occur.
6.6.1.13 An arc-rated balaclava shall be used with an arc-rated face shield when the back of the head is within the arc flash boundary. An arc-rated hood shall be permitted to be used instead of an arc-rated face shield and balaclava.
6.6.1.13.1 An arc-rated hood shall be used when the anticipated incident energy exposure exceeds 12 cal/cm2.
6.6.1.14 Employees must wear protective equipment for the eyes or face when there is a danger of injury to the eyes or face from electric arcs, flashes, or flying objects resulting from electrical explosions. Frames of eyeglasses must be made of non-conductive material and face shields must be of a non-melting type (i.e., polycarbonate). Face shields with wrap-around guarding to protect the face, chin, forehead, ears, and neck area shall be used.
6.6.1.15 Employees shall wear hearing protection whenever working within the arc flash boundary.
6.6.1.16 Heavy-duty leather gloves or arc-rated gloves must be worn over insulating gloves except under the following conditions:
6.6.1.16.1 Under limited use conditions with Class 00 or Class 0 gloves where manipulating small equipment and parts requires greater finger dexterity.
6.6.1.16.2 Under the same conditions stated above, with any other class of glove, it if can be demonstrated that the possibility of physical damage to the gloves is minimal and if the class of glove used is one class higher than that required for the voltage involved.
6.6.1.17 Heavy-duty leather footwear provides some arc flash protection to the feet and shall be used in all exposures greater than 4 cal/cm2.
6.6.1.18 Table B gives examples of typical tasks and the minimum PPE needed to safely perform these tasks.
6.6.2 Use of insulated tools and handling equipment
6.6.2.1 Insulated tools or handling equipment rated for the circuit voltage involved are required when working inside the restricted approach boundary of exposed energized electrical conductors or circuit parts where tools or handling equipment might make accidental contact. Insulated tools shall be protected from damage to the insulating materials.
6.6.2.2 Insulated tools and equipment shall be inspected prior to each use. The inspection shall look for damage to the insulation or damage that may limit the tool from performing its intended function or could increase the potential for an incident.
6.6.2.3 Each individual assigned insulated tools and handling equipment will be responsible for the care and storage of the issued equipment.
6.6.2.4 Insulated hand tools must meet the following requirements:
6.6.2.4.1 Hand tools used as “insulated” must display the international 1000-volt symbol and meet the requirements of ASTM Std. F-1505.
6.6.2.4.2 Insulated hand tools should be stored in a manner to minimize the possibility of damage.
6.6.2.4.3 Before use, insulated hand tools must be visually inspected by the user for defects.
6.6.2.5 Insulated live-line tools must meet the following requirements:
6.6.2.5.1 Insulated live-line tools (hot-sticks) must be used when contact is to be made with circuit parts or equipment that is energized at 600 volts nominal and greater.
6.6.2.5.2 Live-line tools must be constructed to withstand 100,000 volts per foot for five minutes if made of fiberglass reinforced plastic (FRP) and 70,000 volts per foot for three minutes if made of wood.
6.6.2.5.3 Each tool must be visually inspected and wiped clean before use each day.
6.6.2.6 If any defect or contamination is found that could adversely affect the insulating qualities or mechanical integrity of the insulated tool or handling equipment, it must be removed from service and either repaired or discarded. Before any repaired equipment is returned to service, it must be tested per the appropriate ASTM standard by a qualified person.
6.6.2.7 Insulated tools and handling equipment must not be used as a primary means of personal protection. The appropriate electrical PPE must always be worn when using insulated tools and handling equipment on or near energized or potentially energized parts.
6.6.2.8 Insulated fuse “pullers” rate for the circuit voltage must be used to remove or install fuses when the fuse terminals are energized.
6.6.2.9 Ropes and hand-lines used near exposed energized parts must be nonconductive.
6.6.3 Alerting techniques
6.6.3.1 Safety signs, symbols, or accident prevention tags meeting ANSI Z535 requirements must be used, where necessary, to warn employees of electrical hazards that might endanger them.
6.6.3.2 Barricades shall be used in conjunction with safety signs, where necessary, to prevent or limit employee access to work areas containing energized conductors or circuit parts. Conductive barricades may not be used where they might increase the likelihood of exposure to an electrical hazard. Barricades shall be placed no closer than the limited approach boundary. Where the arc flash boundary is greater than the limited approach boundary, barricades shall not be placed closer than the arc flash boundary.
6.6.3.3 If signs and barricades are not an adequate means of warning and protection from electrical hazards, an attendant must be stationed to warn and protect employees.

6.7 In-Service Care and Use of Electrical PPE
6.7.1 General requirements
6.7.1.1 Electrical equipment shall be maintained in accordance with manufacturer’s instructions or industry consensus standards to reduce the risk of failure and the subsequent exposure of employees to electrical hazards.
6.7.1.2 Maintenance, tests, and inspections shall be documented.
6.7.1.3 The requirements of this section apply to insulating gloves, blankets, sleeves, covers, and line hose made of rubber that is approved for use on energized parts.
6.7.1.4 Electrical PPE must be maintained in a safe and reliable condition. Each individual assigned protective equipment will be responsible for the care and storage of the issued equipment.
6.7.2 Care and use of equipment
6.7.2.1 Rubber insulating equipment must be inspected before each day’s use and immediately following any incident that may have caused damage. As part of this inspection, insulating gloves must be given an air test using the roll method. An inspection shall include verification of a suitable test date.
6.7.2.2 Rubber insulating equipment with any of the following defects must not be used:
6.7.2.2.1 A hole, tear, puncture, or cut
6.7.2.2.2 Ozone cutting or ozone checking
6.7.2.2.3 Any embedded foreign object
6.7.2.2.4 Texture changes, such as swelling, softening, hardening, stickiness, or loss of elasticity
6.7.2.2.5 Any other defect that damages the insulating properties of the equipment.
6.7.2.3 Rubber insulating equipment found to have a defect that might affect the insulating properties must be removed from service and tested as described in Table 130.7(C)(7).
6.7.2.4 Rubber insulating equipment must be stored in locations protected from light, temperature extremes, excessive humidity, ozone, and other damaging conditions. In addition, rubber-insulating equipment should not be folded, creased, or distorted in a manner that will cause stretching or compression of the insulating material.
6.7.2.5 Rubber insulating equipment should be periodically cleaned with lukewarm water and a mild soap detergent (non-chlorinated) recommended by the equipment manufacturer. Solvents, oils, and grease should never be used on rubber insulating protective equipment.
6.7.2.6 A certified testing laboratory in accordance with the appropriate ASTM standard must test rubber insulation equipment and the maximum intervals listed in Table 130.7(C )(7). If is the responsibility of each person to ensure that all rubber insulating equipment issued in their care is turned in for testing when usage intervals have expired.
6.7.2.7 Insulating equipment failing to pass inspection or electrical tests must be removed from service and discarded.

6.8 Use of Equipment
6.8.1 Electric power and lighting circuits
6.8.1.1 Routine opening and closing of circuits – Only load rated switches, circuit breakers, or other load rated disconnecting means will be used to open, reverse, or close circuits under load conditions. Non-load break cable connectors, fuses, terminal lugs, or cable splice connections must not be used for such purposes except in emergency situations.
6.8.1.2 Re-closing circuits after protective device operation – When a circuit is de-energized by a protective device, the circuit may not be manually re-energized until it can be determined that the equipment or circuit can be re-energized safely. The repetitive manual re-closing of circuit breakers or re-energizing circuits through replaced fuses is prohibited. However, if it is determined that the automatic operation of an over-current device was caused by an “overload condition” rather than a “fault condition”, then no further inspection of the circuit or equipment is needed before the circuit is re-energized.
6.8.1.3 Overcurrent protection modification – Over-current protection of circuits and conductors must not be modified, even temporarily, beyond that allowed by the installation safety requirements for overcurrent protection in the National Electrical Code (NEC).
6.8.2 Ground Fault Circuit Interrupters (GFCI)
6.8.2.1 GFCIs are utilized to protect personnel when electrical failures of equipment and tools can cause current flow through the human body. GFCIs interrupt this abnormal flow of current at very low values and within a specified period of time, thereby, significantly minimizing injury to personnel.
6.8.2.1.1 All GFCIs used for personnel protection shall be the type that de-energize the circuit at a current magnitude of 5ma+/-1ma. (i.e.., Class A GFCI Interrupter Curve).
6.8.2.1.2 Damaged GFCIs or those that fail to pass the tests outlined below shall not be used. GFCIs shall not be repaired if inoperable.
6.8.2.1.3 Portable tools that are not part of an approved equipment grounding program shall be GFCI protected.
6.8.2.1.4 Testing of GFCIs:
6.8.2.1.4.1 GFCI protected receptacles that are part of a permanent wiring system shall be labeled and traceable to their circuit origin. They shall be checked at the time of the initial installation. The test shall include:
6.8.2.1.4.1.1 A polarity test.
6.8.2.1.4.1.2 Operating the test and reset button.
These tests shall be repeated when repairs are made and the attached equipment is involved in an incident that could have caused damage to the GFCI.
6.8.2.1.4.2 Portable GFCI’s and GFCI’s supplying power in wet locations (portable and permanent), shall be tested prior to use each day. The test shall include:
6.8.2.1.4.2.1 A polarity test.
6.8.2.1.4.2.2 Operating the test and reset button.
6.8.3 Test instruments and equipment
6.8.3.1 Only qualified persons will perform testing on electrical equipment or circuits.
6.8.3.2 All test equipment and related accessories must be visually inspected before each use. If there is evidence of damage that might expose someone to injury, the damaged items must be removed from service until repairs can be rendered.
6.8.3.3 All test equipment and related accessories must be rated for the equipment and circuits to which it will be connected and must be adequately designed for the environment in which it is being used.
6.8.3.4 Test instruments and associated test leads used to verify the absence or presence of voltage shall be maintained to assure functional integrity. The maintenance program shall include functional verification as described in 6.8.3.5.
6.8.3.5 When test instruments are used for testing the absence of voltage on conductors or circuit parts operating at 50 volts or more, the operation of the test instrument shall be verified before and after an absence of voltage, test is performed.
6.8.4 Occasional use of flammable or ignitable materials – Electric equipment capable of igniting flammable materials must not be used where flammable or ignitable materials are occasionally present unless approved by the Nitro Construction Services Hot Work Procedure.

6.9 Additional Requirements and Safe Work Practices
6.9.1 Job briefing
6.9.1.1 When working on circuits or equipment installations that operate at 600 volts nominal and greater, the person in charge of the job or project must conduct a job briefing with the employees involved before any work commences.
6.9.1.2 The briefing should include at a minimum the following requirements:
6.9.1.2.1 Hazards associated with the job.
6.9.1.2.2 Work procedures involved with the job.
6.9.1.2.3 Any special precautions employees should be aware of.
6.9.1.2.4 Energy source controls.
6.9.1.2.5 Personal protective equipment requirements.
6.9.1.3 Job briefings should be sufficient in number and content to adequately address the items listed above.
6.9.1.4 Employees working alone need not conduct a formal job briefing, but should adequately plan and think through the job as if a job briefing had been conducted.
6.9.2 Operating circuit breakers and equipment disconnects
6.9.2.1 It is very important that safe work practices be followed when operating circuit breakers and equipment disconnects.
6.9.2.2 In the event that a circuit breaker is automatically tripped or a fuse is blown, the circuit breaker may not be reset or the fuse replaced until the cause of the circuit trip is known. Unless it is intuitively obvious that the circuit breaker tripped or the fuse blew due to an “overload” situation, a qualified electrician must be contacted to inspect and test the circuit and/or equipment.
6.9.2.3 Once the cause of the circuit breaker trip or blown fuse is determined and/or it has been determined that the circuit breaker or disconnect can be safely operated, the following steps must occur:
6.9.2.3.1 Wear the appropriate PPE for the tasks and hazards involved (See Table B).
6.9.2.3.2 Stand off to one side of the circuit breaker or disconnect – preferably on the hinged side of the cabinet or enclosure door.
6.9.2.3.3 Place the closest hand on the circuit breaker or disconnect lever, turn head so that face points away from the equipment in question, proceed to operate the breaker or disconnect.
6.9.2.4 Only qualified electrical personnel may operate electrical transmission and distribution equipment.
6.9.3 Switching procedures
6.9.3.1 A switching procedure is required for all planned switching events on circuits or equipment installation if there is a possibility of voltage back-feed to the circuits or equipment under consideration. For this reason, switching procedures are usually only applicable to work involving transmission and distribution equipment installation and not utilization equipment installations.
6.9.3.2 A switching procedure is issued to provide a safe work zone for work activity on or near circuits and equipment installations that operate at 600 volts nominal and greater by assuring that these systems have been safely de-energized and grounded.
6.9.3.3 Prior to beginning any switching operations that are covered by the requirements of this section, a detailed switching procedure must be prepared by a qualified person with each step being separately identified and numbered. A second qualified person knowledgeable in the field must review the written switching procedure for accuracy.
6.9.3.4 Only qualified persons may perform switching operations covered under this section.
6.9.3.4.1 If at any time a person performing switching operations is unclear as to the assignment, that person must request assistance immediately.
6.9.3.4.2 Persons performing switching operations must wear the appropriate PPE for the hazards involved.
6.9.3.4.3 The lockout and tagging requirements of the Nitro Construction Services Lockout/Tagout Procedure or the adopted policy of a particular project or client and the specific requirements addressed in these work practices must be followed when performing switching operations covered by this section.
6.9.3.5 Fixed or standing written switching procedures for routine and/or straight forward switching activities are acceptable as long as they are revised as needed and the appropriate approvals are given prior to each switching event.
6.9.4 Battery Systems
6.9.4.1 Prior to any work on a battery system, a risk assessment shall be performed to identify the chemical, electrical shock, and arc flash hazards and assess the risks associated with the type of tasks to be performed.
6.9.4.2 Rechargeable storage batteries used as a source of electrical energy and the areas in which they are housed, require focused practices to minimize risk to personnel during inspection or servicing activities.
6.9.4.3 Only approved insulated hand tools will be used when working on or near exposed battery terminals.
6.9.4.4 Personnel shall not wear electrically conductive objects such as jewelry while working on a battery system.
6.9.4.5 Electrolytes will only be handled by personnel properly protected with eye protection (chemical splash goggles and face shields), long sleeves, and rubber gloves.
6.9.4.6 Exhaust systems must be maintained operable to minimize the risk of hazardous and toxic fume accumulation.
6.9.4.7 Portable or stationary eyewash facilities shall be available to employees within the work area that are capable of drenching or flushing the eyes and body for the duration necessary to the hazard.
6.9.4.8 Facilities for flushing and neutralizing spilled electrolytes and for fire protection must be available.
6.9.5 Underground Electrical Installations
6.9.5.1 Some underground electrical installation locations may be considered confined spaces, and therefore the requirement of the Nitro Construction Services Confined Space Entry Procedure will need to be followed.
6.9.5.2 Before excavation starts where there exists a reasonable possibility of contacting electrical lines or equipment, the employer shall take the necessary steps to contact the appropriate owners or authorities to identify and mark the location of the electrical lines or equipment. When it has been determined that a reasonable possibility of contacting electrical lines or equipment exists, appropriate safe work practices and PPE shall be used during excavation.
6.9.5.3 Before cutting or drilling into equipment, floors, walls, or structural elements where a likelihood of contacting energized electrical lines or parts exists, the employer shall perform a risk assessment to:
6.9.5.3.1 Identify and mark the location of conductors, cables, raceways, or equipment.
6.9.5.3.2 Create an electrically safe work condition.
6.9.5.3.3 Identify safe work practices and PPE to be used
6.9.5.4 Ladders or other climbing devices must be used to enter and exit manholes or subsurface vaults exceeding 4 feet.
6.9.5.5 When multiple cables exist in the work area, the cable to be worked on must be positively identified. Cables other than the one being worked on must be protected from damage.
6.9.5.6 Energized cables to be moved must be inspected for defects.
6.9.5.7 When a cable in a manhole or subsurface vault has an abnormality that could lead to or be an indication of an impending fault (such as swollen joints or hot localized surface temperature), the affected cable must be de-energized before any person can begin work. If de-energizing the cable is not feasible, a protective shield or barriers must be applied that are capable of containing the adverse effects of possible cable failure.
6.9.5.8 When work is performed on buried able or on cable in manholes and subsurface vaults, metallic sheath continuity must be maintained or the cable sheath must be treated as energized.
6.9.6 Do’s and Don’ts
6.9.6.1 DO Regard all electrical conductors as a potential hazard.
6.9.6.2 DO switch off lighting circuits before replacing burned-out lamps.
6.9.6.3 DO NOT use metal rules around energized equipment.
6.9.6.4 DO NOT use screwdrivers, etc. to actuate electrical power contacts.
6.9.6.5 DO NOT stand directly in front of disconnect switches or high-voltage starters when operating them.
6.9.6.6 DO NOT energize oil-filled combination starters or oil-filled disconnect switches with contacts open to the air. (Have adequate oil level in the tank, and the tank secured in position before energizing).
6.9.7 Emergency Procedures
6.9.7.1 Employees exposed to shock hazards shall be trained in methods of the release of victims from contact with exposed energized electrical conductors or circuit parts.
6.9.7.2 Employees shall be regularly instructed in methods of first aid and emergency procedures. Training of employees in approved methods of resuscitation, including CPR, shall be certified by the employer annually.
6.9.7.3 Employee training must ensure that each employee understands the steps necessary to release a victim who might be in contact with the energized conductor. If anyone should come in contact with an energized conductor and are unable to release their grip on the conductor, do not attempt to pull the victim free with bare hands. The following guidance is provided:
6.9.7.3.1 De-energize the circuit by opening the nearest breaker to the point where the victim is touching. (Location of the proper circuit breaker should be determined before work is started.) Remove the victim from the circuit.
6.9.7.3.2 Summons emergency help immediately.
6.9.7.3.3 Keep the victim quiet. Do not let them walk and keep them warm.

6.10 Energized Work Permit
6.10.1 When working on energized electrical conductors or circuit parts that are not placed in an electrically safe condition, work to be performed shall be considered energized electrical work and shall be performed by written permit only.
6.10.2 The energized electrical work permit shall include, but not be limited to, the following items:
6.10.2.1 A description of the circuit and equipment to be worked on and their location.
6.10.2.2 Justification for why the work must be performed in an energized condition.
6.10.2.3 A description of the safe work practices to be employed.
6.10.2.4 Results of the shock risk assessment.
6.10.2.5 Determination of shock protection boundaries.
6.10.2.6 Results of the arc flash risk assessment.
6.10.2.7 The arc flash protection boundary.
6.10.2.8 The necessary PPE to safely perform the assigned task.
6.10.2.9 Means employed to restrict the access of unqualified persons from the work area.
6.10.2.10 Evidence of completion of a job briefing, including a discussion of any job-specific hazards.
6.10.2.11 Energized work approval (authorizing or responsible management, safety officer or owner, etc.) signature(s).
6.10.3 Permit forms – The original copy must remain at the job site while the work is being performed.

7.0 TRAINING
7.1 General
7.1.1 Nitro Construction Services will provide training to all Nitro Construction Services employees who face a risk of electrical shock or injury when working on or near exposed energized parts or parts that may become energized. These employees will be trained on this procedure at least annually as it pertains to their respective job assignments.
7.1.2 All qualified persons will be trained on the following:
7.1.2.1 The skills and techniques needed to distinguish exposed energized electrical conductors and circuit parts from other parts of electrical equipment.
7.1.2.2 The skills and techniques needed to determine the nominal voltage of exposed energized electrical conductors and circuit parts.
7.1.2.3 The minimum approach distances as specified in this procedure and the corresponding voltages to which the qualified person will be exposed.
7.1.2.4 The decision-making process necessary to determine the degree and extent of the hazard and the PPE and job planning necessary to perform the task safely.
7.1.2.5 Tasks that are performed less often than once per year shall require retraining before the performance of the work practices.
7.1.2.6 Employees shall be trained to select an appropriate test instrument and shall demonstrate how to use a device to verify the absence of voltage, including interpreting indications provided by the device. Training shall include information that enables the employee to understand all limitations of each specific test instrument that may be used.
7.1.2.7 Employees shall be regularly instructed in methods of first aid and emergency procedures, such as approved methods of resuscitation if their duties warrant such training. Training of employees in approved methods of resuscitation, including CPR, shall be certified annually by the employer.
7.1.2.8 A worker who has not performed a work task involved with work on or near an exposed energized electrical conductor or circuit part for one or more years is considered to be unqualified for the task until the worker has been retrained.
7.1.3 All persons permitted to work within the restricted approach boundary of exposed energized electrical conductors and circuit parts operating at 50 volts or more shall be qualified and, at a minimum, be additionally trained in the following:
7.1.3.1 Skills and techniques are necessary to distinguish exposed energized electrical conductors and circuit parts from other parts of electrical equipment.7.1.3.2 Skills and techniques are necessary to determine the nominal voltage of exposed energized electrical conductors and circuit parts.
7.1.3.3 Approach distances specified in Table A and the corresponding voltages to which the qualified person will be exposed.
7.1.3.4 Decision-making process necessary to determine the degree and extent of the hazard and the personal protective equipment and job planning necessary to perform the task safely.
7.1.4 Unqualified persons may require varying levels of training depending on their respective job assignments and exposure to electrical hazards. Examples of unqualified persons that may require additional electrical safety training include process operators, crane, and mechanical equipment operators, scaffold builders, painters, etc. Training for unqualified persons may include the following:
7.1.4.1 The ability to identify potentially hazardous electrical energy and its potential impact on workplace conditions.
7.1.4.2 Safe working clearances for persons and mechanical or vehicular equipment.
7.1.4.3 Proper handling and use of portable electrical equipment.
7.1.4.4 Proper techniques for operating circuit breakers and equipment disconnects.

7.2 Certification and Retraining
7.2.1 Supervision and inspections must be used to verify that each person is complying with the safe work practices required by this procedure.
7.2.2 Certification will be made when a person demonstrates proficiency in these work practices. Documentation of this certification must be maintained for the duration of the person’s employment at Nitro Construction Services, LLC.
7.2.3 People must receive additional training or retraining under any of the following conditions:
7.2.3.1 If supervision or annual inspections indicate a person is not complying with these safety-related work practices.
7.2.3.2 If new types of equipment, new technology, or changes in work assignments alter the existing safe work practices.
7.2.3.3 If a person must utilize safe work practices that are not normally used during their regular job duties.
7.2.3.4 If a person is not complying with safety-related work practices.
7.2.4 Retraining shall be performed in intervals not to exceed 3 years.

7.3 Training Documentation
7.3.1 The employer shall document that each employee has received the training required by this section.
7.3.2 The documentation shall be made when the employee demonstrates proficiency in the work practices involved.
7.3.3 The documentation shall contain the content of the training, each employee’s name, and the dates of the training.

8.0 ELECTRICAL SAFETY AUDITING
8.1 This Electrical Safe Work Practices procedure and program shall be audited annually to ensure that the principles and procedures of the electrical safety program are being followed.
8.2 Where the audit determines that the principles and procedures of this procedure are not being followed, appropriate actions shall be taken (i.e., refresher training, procedure revisions, etc.)

9.0 APPENDICES/TABLES
9.1 Table 130.4(D)(a) – Approach Boundaries to Energized Electrical Conductors or Circuit Parts for Shock Protection for AC Systems
9.2 Table 130.4(D)(b) – Approach Boundaries to Energized Electrical Conductors or Circuit Parts for
Shock Protection for DC Systems
9.3 Table 130.(C )(15)(a) – Arc Flash Hazard PPE Categories for AC Systems
Table 130.(C) (15)(b) – Arc Flash Hazard PPE Categories for DC Systems
9.4 Table 130.7(C )(15)(c ) – Personal Protective Equipment (PPE)
9.5 Table 130.7(C )(7) – Rubber Insulating Equipment, Maximum Test Intervals
9.6 Table D – Energized Electrical Work Permit
9.7 Table E – General Categories of Electrical Hazards
9.8 NCS Form 055 – Bucket Truck Safety Checklist
9.9 NCS Form 056 – Digger Truck Safety Checklist